CONTROL PANELS
22
Operational Details and Engineering Diagram
FIL STATE
• Display show fil
• Alarm light is on until AL.1 is off
• Heater is disabled
• Pumps are disabled
• Soap Pump is disabled
START/STOP
Button pressed
Alarm 1 Status (al.1)
On
Timer t and t2 start
RUN STATE
• Display shows water temperature
• Change Water Light is off
• Heater is enabled
• Pumps are ON
• Soap Pump is enabled
Off
Alarm 2 on (al.2)
AL2 STATE
• Display Shows al.2
• Alarm light is on
• Heater is disabled
• Pumps are disabled
• Soap Pump is enabled
• Timer t is paused
• Timers t2 and t3 do not pause
Alarm 2 off (al.2)
Alarm 1 on (al.1)
START/STOP
Button pressed
START/STOP
Button pressed
STOP STATE
• Display shows water temperature
• Change Water Light is off
• Heater is enabled
• Pumps are OFF
• Soap Pump is enabled
• Timer t is paused
• Timers t2 and t3 do not pause
Timer t expires
Drain STATE
• Display shows drn
• Change Water Light flashes
• Heater is enabled
• Pumps are OFF
• Soap Pump is OFF
Alarm 1 on (AL.1)
UP + START/STOP
Buttons pressed for
15 seconds